Doc# E149701 7 - 4
7: Using the I/O Option Cards
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
The general specifications are as follows:
Operating temperature: (-20 to +70)° C
Storage temperature: (-40 to +80)° C
Relative air humidity: Maximum 95%, non-condensing
EMC - Immunity Interference: EN61000-4-2
Weight: 1.6oz
Dimensions (inch) W x H x L: 0.72 x 2.68 x 3.26
External connection: AWG 12-26/(0.29 - 3.31) mm
2
5 pin, 0.200” pluggable terminal block
7.4.2: Default Configuration:
The Shark® 200 meter automatically recognizes the installed Option card during
power up. If you have not programmed a configuration for the card, the unit defaults
to the following outputs:
Channel 1 +Watts, +1800 Watts => +1mA
-Watts, - 1800 Watts => -1mA
Channel 2 +VARs, +1800 VARs => +1mA
- VARs, -1800 VARs => -1mA
Channel 3 Phase A Voltage WYE, 300 Volts => +1mA
Phase A Voltage Delta, 600 Volts => +1mA
Channel 4 Phase A Current, 10 Amps => +1mA