B: Modbus Map and Retrieving Logs
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
limit after the setpoint has been exceeded. This prevents "babbling" limits, which can
be caused by the limit value fluttering over the setpoint, causing it to go in and out of
limit continuously.
• Identifier: The first modbus register of the value that is being watched by this limit.
While any modbus register is valid, only values that can have a Full Scale will be
used by the Shark® 200 meter.
• Above Setpoint: The percent of the Full Scale above which the value for this limit
will be considered "out."
• Valid in the range of -200.0% to +200.0%
• Stored as an integer with 0.1 resolution. (Multiply % by 10 to get the integer,
divide integer by 10 to get %. For example, 105.2% = 1052.)
• Above Hysteresis: The percent of the Full Scale below which the limit will return
"into" limit, if it is out. If this value is above the Above Setpoint, this Above limit will
be disabled.
• Valid in the range of -200.0% to +200.0%.
• Stored as an integer with 0.1 resolution. (Multiply % by 10 to get the integer,
divide integer by 10 to get %. For example, 104.1% = 1041.)
• Below Setpoint: The percent of the Full Scale below which the value for this limit
will be considered "out."
• Valid in the range of -200.0% to +200.0%.
• Stored as an integer with 0.1 resolution. (Multiply % by 10 to get the integer,
divide integer by 10 to get %. For example, 93.5% = 935.)
• Below Hysteresis: The percent of the Full Scale above which the limit will return
"into" limit, if it is out. If this value is below the Below Setpoint, this Below limit will
be disabled.
• Valid in the range of -200.0% to +200.0%.