Electro Industries Shark 200T Especificaciones Pagina 231

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 246
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 230
Doc# E149701 C - 3
C: DNP Mapping
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
communication port will accept Modbus RTU frames only. To make this port go back
to DNP protocol, the unit must be power-recycled. Section C.7 shows the con-
structed frame to perform DNP to Modbus RTU protocol change.
C.5: Error Reply
In the case of an unsupported function, or any other recognizable error, an error reply
will be generated from the Shark® 200 meter to the Primary station (the requester).
The Internal Indicator field will report the type of error: unsupported function or bad
parameter.
The broadcast acknowledge and restart bit, are also signaled in the internal indicator
but they do not indicate an error condition.
C.6: Shark
®
200 Meter’s DNP Register Map
Object 10 - Binary Output States
Object 12 - Control Relay Outputs
Object Point Var Description Format Range Multiplier Units Comments
10 0 2 Reset Energy
Counters
BYTE Always 1 N/A None Read by Class
0 or with qual-
ifier 0, 1, 2, or
6
10 1 2 Change to
Modbus RTU
Protocol
BYTE Always 1 N/A None Read by Class
0 or with qual-
ifier 0, 1, 2, or
6
10 2 2 Reset Demand
Cntrs (Max /
Min )
BYTE Always 1 N/A None Read by Class
0 or with qual-
ifier 0, 1, 2, or
6
Object Point Var Description Format Range Multiplier Units Comments
12 0 1 Reset Energy
Counters
N/A N/A N/A none Responds to Function 5
(Direct Operate), Quali-
fier Code 17x or 28x,
Control Code 3, Count
0, On 0 msec, Off 1
msec ONLY.
12 1 1 Change to
Modbus RTU
Protocol
N/A N/A N/A none Responds to Function 6
(Direct Operate - No
Ack), Qualifier Code
17x, Control Code 3,
Count 0, On 0 msec,
Off 1 msec ONLY.