Doc# E149701 4 - 6
4: Electrical Installation
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
4.5: Voltage and Power Supply Connections
Voltage inputs are connected to the back of the unit via optional wire connectors. The
connectors accommodate AWG# 12 -26/ (0.129 - 3.31)mm
2
.
Figure 4.4: Meter Connections
4.6: Ground Connections
The meter’s Ground terminals should be connected directly to the installation’s
protective earth ground. Use AWG# 12/2.5 mm
2
wire for this connection.
4.7: Voltage Fuses
EIG recommends the use of fuses on each of the sense voltages and on the control
power, even though the wiring diagrams in this chapter do not show them.
• Use a 0.1 Amp fuse on each voltage input.
• Use a 3 Amp Slow Blow fuse on the power supply.
EIG offers the EI-CP Panel meter protective fuse kit, which can be ordered from EIG’s
webstore: www.electroind.com/store. Select Fuse Kits from the list on the left side of
the webpage.
