B: Modbus Map and Retrieving Logs
Doc# E149701 MM-34
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1) Format Range (Note 6) Units or Resolution Comments # Reg
Modbus Address
Hex Decimal
80F3 - 80F3 33012 - 33012 Fast pulse input selector UINT16 bit-mapped
p------- -----nnn
When value 'nnn' is non-zero, it determines which of the
card inputs will be a fast pulse detection input.
The polarity bit 'P' tells the event to be detected: 1=open-
to-close; 0=close-to-open. There is no “any-change”
detection mode.
1
80F4 - 8126 33013 - 33063 Reserved Reserved 51
Block Size: 63
Second Overlay write only in PS update mode
8127 - 812E 33064 - 33071 Input#1 Label ASCII 16 char 8
812F - 8136 33072 - 33079 Input#1 Low State Name ASCII 16 char 8
8137 - 813E 33080 - 33087 Input#1 High State Name ASCII 16 char 8
813F - 8156 33088 - 33111 Input#2 Label and State Names 24
8157 - 8186 33112 - 33159 Reserved 48
8187 - 818E 33160 - 33167 Relay#1 Label ASCII 16 char 8
818F - 8196 33168 - 33175 Relay#1 Open State Name ASCII 16 char 8
8197 - 819E 33176 - 33183 Relay#1 Closed State Name ASCII 16 char 8
819F - 81B6 33184 - 33207 Relay#2 Label and State Names 24
81B7 - 81E6 33208 - 33255 Reserved 48
81E7 - 81EE 33256 - 33263 Input#1 Accumulator Label ASCII 16 char 8
81EF - 81F6 33264 - 33271 Input#2 Accumulator Label ASCII 16 char 8
8208 - 8208 33289 - 33289 Input#2 Accumulator Kt UINT16 bit-mapped
ddVVVVVV VVVVVVVV
1
8209 - 8326 33290 - 33575 Reserved 286
Block Size: 512
Second Overlay write only in PS update mode
8127 - 812E 33064 - 33071 Input#1 Label ASCII 16 char 8
812F - 8136 33072 - 33079 Input#1 Low State Name ASCII 16 char 8
8137 - 813E 33080 - 33087 Input#1 High State Name ASCII 16 char 8
813F - 8156 33088 - 33111 Input#2 Label and State Names 24
8157 - 816E 33112 - 33135 Input#3 Label and State Names 24
816F - 8186 33136 - 33159 Inp
ut#4 Label and State Names 24
8187
- 818E 33160 - 33167 Output#1 Label ASCII 16 char 8
818F - 8196 33168 - 33175 Output#1 Open State Name ASCII 16 char 8
8197 - 819E 33176 - 33183 Output#1 Closed State Name ASCII 16 char 8
819F - 81B6 33184 - 33207 Output#2 Label and State Names 24
81B7 - 81CE 33208 - 33231 Output#3 Label and State Names 24
81CF - 81E6 33232 - 33255 Output#4 Label and State Names 24
81E7 - 81EE 33256 - 33263 Input#1 Accumulator Label ASCII 16 char 8
81EF - 81F6 33264 - 33271 Input#2 Accumulator Label ASCII 16 char 8
81F7 - 81FE 33272 - 33279 Input#3 Accumulator Label ASCII 16 char 8
81FF - 8206 33280 - 33287 Input#4 Accumulator Label ASCII 16 char 8
same as Input#1
same as Output#1
same as Output#1
same as Output#1
KT power factor for the Pulse Output
"V" is raw power value in Wh/pulse from 0 to 9999.
"dd"=decimal point position: 00=0.XXXX, 01=X.XXX,
10=XX.XX, 11= X.XXX.
Settings Registers for Digital I/O Pulse Output Card
same as Input#1
same as Input#1
Settings Registers for Digital I/O Relay Card
same as Input#1
same as Relay#1