Doc# E149701 8 - 7
8: Using the INP100S Network Card
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
8.4.2.1: Upgrading the Ethernet Card’s Firmware
From one of the Shark® 200 meter’s webpages:
1. Click Meter Information on the left side of the webpage.
2. Click Upgrade Network Card (bottom box on the right). You will see the window
shown below.
NOTE: In order to upgrade the Network (Ethernet) Card, you must be using the PC
on which the upgrade file is stored.
3. Click the Browse button to locate the Upgrade file. Make sure that you select the
INP100S option card upgrade file. If you upgrade with an INP300S upgrade file, the
card will not work.
4. Enter the safety code (supplied with the Upgrade file) and the password: the
default is n3tUp!0Ad for firmware runtime version 3.35 or higher; and eignet2009
for earlier firmware runtime versions. See the note on page 8-6.
5. Click Submit. The upgrade starts immediately (it may take several minutes to
complete). Once the upgrade is complete, you will see a confirmation message.
CAUTION! Note the Warning message on the screen. If there is a power interruption
during upgrade, please call EIG’s Technical Support department at 516-334-0870 for
assistance.