Doc# E149701 2 - 14
2: Meter Overview and Specifications
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Isolation
All Inputs and Outputs are galvani-
cally isolated to 2500 VAC
Environmental Rating
Storage: (-20 to +70)
o
C
Operating: (-20 to +70)
o
C
Humidity: to 95% RH Non-condensing
Faceplate Rating: NEMA12 (Water Resistant), mount-
ing gasket included
Measurement Methods
Voltage, current: True RMS
Power: Sampling at over 400 samples per
cycle on all channels
Update Rate
Watts, VAR and VA: Every 6 cycles (e.g., 100ms @ 60
Hz)
All other parameters: Every 60 cycles (e.g., 1 s @ 60 Hz)
1 second for Current Only measure-
ment, if reference Voltage is not
available
Communication
Standard:
1. RS485 port through backplate
2. IrDA port through faceplate
3. Energy pulse output through backplate and Infrared LED through faceplate