Doc# E149701 2 - 3
2: Meter Overview and Specifications
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
• Sampling rate of up to 512 samples per cycle
for waveform recording
• Transformer/Line Loss compensation (see
Chapter 5 and Appendix B in the Communica-
tor EXT
TM
User Manual for instructions on
using this feature*)
• CT/PT compensation (see Chapter 5 in the
Communicator EXT
TM
User Manual for instruc-
tions on using this feature*)
* Access the Communicator EXT
TM
User Manual from the Communicator EXT
TM
Product CD or by clicking Help>Contents from the Communicator EXT
TM
Main
screen.
In addition to the Shark® 200 meter/transducer configuration, a Shark® 200T trans-
ducer configuration is available. The Shark® 200T transducer is a digital transducer
only unit, providing RS485 communication via Modbus RTU, Modbus ASCII or DNP 3.0
protocols. The unit is designed to install using DIN Rail mounting (see Section 3.4 for
Shark® 200T transducer mounting information).
2.1.1: Voltage and Current Inputs
Universal Voltage Inputs
Voltage inputs allow measurement up to Nominal 576VAC (Phase to Reference) and
721VAC (Phase to Phase). This insures proper meter safety when wiring directly to
high Voltage systems. The unit will perform to specification on 69 Volt, 120 Volt, 230
Volt, 277 Volt, and 347 Volt power systems.
NOTE: Higher Voltages require the use of potential transformers (PTs).
Current Inputs
The unit supports a 5 Amp or a 1 Amp secondary for current measurements.
NOTE: The secondary current must be specified and ordered with the meter.
The current inputs are only to be connected to external current transformers.