B: Modbus Map and Retrieving Logs
Doc# E149701 MM-16
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1) Format Range (Note 6) Units or Resolution Comments # Reg
Modbus Address
Hex Decimal
254A - 254C 9547 - 9549 Symmetrical Comp Phase, + Seq, Max
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
254D - 254F 9550 - 9552 Symmetrical Comp Phase, - Seq, Max
Timestamp
TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2550 - 2552 9553 - 9555 Unbalance, 0 Seq, Max Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2553 - 2555 9556 - 9558 Unbalance, - Seq, Max Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
2556 - 2558 9559 - 9561 Current Unbalance, Max Timestamp TSTAMP 1Jan2000 - 31Dec2099 1 sec 3
Block Size: 159
read-only
270F - 270F 10000 - 10000 Class ID and card status UINT16 bit-mapped
undv-----cccctttt
Flags active if bit is set: u=unsupported card; n=card
need configuration; d=card is using default configuration;
v=communication with card is ok
Field: cccc=class of installed card.
Field tttt=type of card. See note 22
1
2710 - 2710 10001 - 10001 Reserved Reserved 1
2711 - 2718 10002 - 10009 Card name ASCII 16 char none ASCII name of the installed card 8
2719 - 2720 10010 - 10017 Serial number ASCII 16 char none Serial Number in ASCII of the installed card 8
2721 - 2722 10018 - 10019 Version ASCII 4 char none Version in ASCII of the hardware of the installed card. 2
2723 - 2746 10020 - 10055 Reserved Reserved 36
2747 - 274A 10056 - 10059 Firmware Versions ASCII 4 char each none Firmware versions for option cards. Each version is a 4
character string, left justified and padded with spaces.
Interpretation depends on the specific card in the slot:
Analog
uses the second 2 registers for its version. The
first 2 registers are zero.
Network
uses the first 2 registers for its RUN version, the
second 2 for its BOOT version.
No other cards report versions; both registers are zero.
4
274B - 274E 10060 - 10063 Reserved Reserved 4
Block Size: 64
Read-only
274F - 274F 10064 - 10064 Current speed and format UINT16 bit-mapped
-abcde-- fghijklm
Bps: a=57600; b=38400; c=19200; d=14400; e=9600
Stop bits 'f': cleared 1 stop bit, set 2 stop bits
Parity: g=even; h=odd; i=none
Data bits: j=8; k=7; l=6; m=5
1
2750 - 2750 10065 - 10065 Reserved UINT16 bit-mapped Reserved 1
2751 - 2751 10066 - 10066 Current protocol UINT16 bit-mapped
-------- -----ppp-
ppp=protocol
100=DNP3; 010=Ascii Modbus; 001=Rtu Modbus
1
2752 - 2752 10067 - 10067 Current reply delay UINT16 0 to 65535 milliseconds Delay to reply to a Modbus transaction after receiving it. 1
2753 - 2756 10068 - 10071 Reserved Reserved 4
Block Size: 8
read-only
2757 - 2790 10072 - 10129 Data and Control Block for Option Card 1.
Meaning of registers depends on installed card. -
- see below
Register assignments depend on which type of card is in
the slot. See overlays below.
58
Block Size: 66
Current Communication Settings for Option Card 1
Data and Control Blocks for Option Card 1
Option Card 1 Section
Card Identification and Configuration Block (Note 14)
Comentarios a estos manuales