B: Modbus Map and Retrieving Logs
Doc# E149701 MM-28
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1) Format Range (Note 6) Units or Resolution Comments # Reg
Modbus Address
Hex Decimal
7D21 - 7D21 32034 - 32034 Input Accumulators Scaling UINT16 bit-mapped
-------- 22221111
1
7D22 - 7D22 32035 - 32035 Relay Accumulators Scaling UINT16 bit-mapped
-------- 22221111
1
7D23 - 7D23 33036 - 33036 Fast pulse input selector UINT16 bit-mapped
p------- -----nnn
When value 'nnn' is non-zero, it determines which of the
card inputs will be a fast pulse detection input.
The polarity bit 'P' tells the event to be detected: 1=open-
to-close; 0=close-to-open. There is no “any-change”
detection mode.
1
7D24 - 7D3E 32037 - 32063 Reserved Set to 0. 27
Block Size: 63
First Overlay write only in PS update mode
7D00 - 7D00 32001 - 32001 Input#1 - 4 bindings & logging enables UINT16 bit-mapped
44443333 22221111
One nibble for each input.
Assuming "abcc" as the bits in each nibble:
"a": select this input for EOI (End Of Interval)pulse
sensing.
"b": log this input when pulse is detected
"cc": Input event trigger mode - Contact sensing method;
00 = none; 01 = open to close; 10 = close to open; 11 =
any change.
Every input has an associated internal accumulator (See
input Accumulator Scaling), which is incremented every
time the input changes according with the trigger mode
crieteria “cc”
1
7D01 - 7D01 32002 - 32002 Source for Pulse Ouput#1 UINT16 enumeration
-----ppp ----vvvv
" ppp" (Phase) : 000 = none, 001 = Phase A, 010 =
Phase B, 011 = Phase C, 100 = All Phases, 101 = Pulse
from EOI(End Of Interval).
"vvvv"(Value) :
0000= none,
0001 = Wh,
0010 = +Wh,
0011 = -Wh,
0100= Varh,
0101 = +Varh,
0110 = -Varh,
0111 = VAh,
1000= Received Wh,
1001= Delivered Wh,
1010= Inductive Varh,
1011 = Capacitive Varh
1
7D02 - 7D02 32003 - 32003 Kt [Wh/pulse] factor for Pulse Output#1 UINT16 bit-mapped
ddVVVVVV VVVVVVVV
"V…V" = not scaled energy value per pulse, from 0 to
9999.
"dd"= decimal point position: 00=0.XXXX, 01=X.XXX,
10=XX.XX, 11= X.XXX.
1
7D03 - 7D04 32004 - 32005 Output#2 Assignment and Kt UINT16 2
7D05 - 7D06 32006 - 32007 Output#3 Assignment and Kt UINT16 2
Settings Registers for Digital I/O Pulse Output Card
same as Output #1
same as Output #1
4 bits per input or output accumulator
The nibble informs what should be the scaling of the
accumulator 0=no-scaling, 1=0.1, 2=0.01, 3= 1m,
4=0.1m, 5=0.01m, 6=1u, 7=0.1u; the value 15 disable
the accumulator.
Example: suppose that the internal input accumulator #1
is 12345, and its corresponding scaling setting is “0011”
(3 decimal). Then, the accumulator will be read as:
Scaling 3, means 1m or 0.001.
Scaled accumulator = 12345 * 0.001 = 12 (Twelve).
Vista de pagina 227