B: Modbus Map and Retrieving Logs
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
NOTES:
• When auto-increment is enabled, this value will automatically increment
so that the window will "page" through the records, increasing by
RecordsPerWindow each time that the last register in the window is read.
• When auto-increment is not enabled, this value must be written-to
manually, for each window to be retrieved.
• Log Retrieval Data Window: The actual data of the records, arranged according to
the above settings.
B.5.4: Log Retrieval
Log Retrieval is accomplished in 3 basic steps:
1. Engage the log.
2. Retrieve each of the records.
3. Disengage the log.
B.5.4.1: Auto-Increment
In EIG's traditional Modbus retrieval system, you write the index of the block of data
to retrieve, then read that data from a buffer (window). To improve the speed of
retrieval, the index can be automatically incremented each time the buffer is read.
In the Shark® 200 meter, when the last register in the data window is read, the
record index is incremented by the Records per Window.
B.5.4.2: Modbus Function Code 0x23
QUERY
Field Name
Example (Hex)
Slave Address 01
Function 23
Starting Address Hi C3
Starting Address Lo 51