Doc# E149701 2 - 17
2: Meter Overview and Specifications
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
1
• For 2.5 element programmed units, degrade accuracy by an additional 0.5% of
reading.
• For 1A (Class 2) Nominal, degrade accuracy to 0.5% of reading for watts and
energy; all other values 2 times rated accuracy.
• For 1A (Class 2) Nominal, the input current range for accuracy specification is
20% of the values listed in the table.
2
For unbalanced Voltage inputs where at least one crosses the 150V auto-scale
threshold (for example, 120V/120V/208V system), degrade the accuracy to 0.4%
of reading.
3
With reference Voltage applied (VA, VB, or VC). Otherwise, degrade accuracy to
0.2%. See hookup diagrams 8, 9, and 10 in Chapter 4.
4
At least one Voltage input (minimum 20 VAC) must be connected for THD
measurement on current channels.
Apparent Energy Total
[VAh]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
Power Factor
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
Frequency [Hz] +/- 0.001 Hz (45 to 65) Hz
Total Harmonic Distortion
[%]
+/- 2%
1, 4
(0.5 to 10)A or (69 to
480)V, measurement
range (1 to 99.99)%
Load Bar
+/- 1 segment
1
(0.005 to 6) A
Table 2:
Parameter Accuracy Accuracy Input Range1