B: Modbus Map and Retrieving Logs
Doc# E149701 MM-33
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1) Format Range (Note 6) Units or Resolution Comments # Reg
Modbus Address
Hex Decimal
First Overlay write only in PS update mode
80E8 - 80E8 33001 - 33001 Input#1 - 4 bindings & logging enables UINT16 bit-mapped
44443333 22221111
One nibble for each input.
Assuming "abcc" as the bits in each nibble:
"a": select this input for EOI (End Of Interval)pulse
sensing.
"b": log this input when pulse is detected
"cc": Input event trigger mode - Contact sensing method;
00 = none; 01 = open to close; 10 = close to open; 11 =
any change.
Every input has an associated internal accumulator (See
input Accumulator Scaling), which is incremented every
time the input changes according with the trigger mode
crieteria “cc”
1
80E9 - 80E9 33002 - 33002 Source for Pulse Ouput#1 UINT16 enumeration
-----ppp ----vvvv
" ppp" (Phase) : 000 = none, 001 = Phase A, 010 =
Phase B, 011 = Phase C, 100 = All Phases, 101 = Pulse
from EOI(End Of Interval).
"vvvv"(Value) :
0000= none,
0001 = Wh,
0010 = +Wh,
0011 = -Wh,
0100= Varh,
0101 = +Varh,
0110 = -Varh,
0111 = VAh,
1000= Received Wh,
1001= Delivered Wh,
1010= Inductive Varh,
1011 = Capacitive Varh
1
80EA - 80EA 33003 - 33003 Kt [Wh/pulse] factor for Pulse Output#1 UINT16 bit-mapped
ddVVVVVV VVVVVVVV
"V…V" = not scaled energy value per pulse, from 0 to
9999.
"dd"= decimal point position: 00=0.XXXX, 01=X.XXX,
10=XX.XX, 11= X.XXX.
1
80EB - 80EC 33004 - 33005 Output#2 Assignment and Kt UINT16 2
80ED - 80EE 33006 - 33007 Output#3 Assignment and Kt UINT16 2
80EF - 80F0 33008 - 33009 Output#4 Assignment and Kt UINT16 2
80F1 - 80F1 33010 - 33010 Input Accumulators Scaling UINT16 bit-mapped
44443333 22221111
1
80F2 - 80F2 33011 - 33011 Output Accumulators Scaling UINT16 bit-mapped
44443333 22221111
1
80F3 - 80F3 33012 - 33012 Fast pulse input selector UINT16 bit-mapped
p------- -----nnn
When value 'nnn' is non-zero, it determines which of the
card inputs will be a fast pulse detection input.
The polarity bit 'P' tells the event to be detected: 1=open-
to-close; 0=close-to-open. There is no “any-change”
detection mode.
1
80F4 - 8126 33013 - 33063 Reserved Reserved 51
Block Size: 63
Settings Registers for Digital I/O Pulse Output Card
same as Output #1
same as Output #1
same as Output #1
see Relay Card above