Electro Industries Shark 200T Especificaciones Pagina 252

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 298
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 251
Doc# E149701 C - 10
C: DNP Mapping
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Object 30 - Analog Inputs (Secondary Readings)
Read with Object 30, Var 4, and Qualifiers 0, 1, 2, or 6. (Included in Class 0
responses.)
NOTE: Object 30 may be either primary or secondary readings per a user setup
option. See the page C-12(C-13?) for the primary version of Object 30.
Object Point Var Description Format Range Multiplier Units Comments
30 0 4 Meter Health SINT16 0 or 1 N/A None 0 = OK
30 1 4 Volts A-N SINT16 0 to 32767 (150 / 32768) V Values above
150V
secondary
read 32767.
30 2 4 Volts B-N SINT16 0 to 32767 (150 / 32768) V
30 3 4 Volts C-N SINT16 0 to 32767 (150 / 32768) V
30 4 4 Volts A-B SINT16 0 to 32767 (300 / 32768) V Values above
300V
secondary
read 32767.
30 5 4 Volts B-C SINT16 0 to 32767 (300 / 32768) V
30 6 4 Volts C-A SINT16 0 to 32767 (300 / 32768) V
30 7 4 Amps A SINT16 0 to 32767 (10 / 32768) A Values above
10A
secondary
read 32767.
30 8 4 Amps B SINT16 0 to 32767 (10 / 32768) A
30 9 4 Amps C SINT16 0 to 32767 (10 / 32768) A
30 10 4 Watts, 3-Ph
total
SINT16 -32768 to
+32767
(4500 /
32768)
W
30 11 4 VARs, 3-Ph
total
SINT16 -32768 to
+32767
(4500 /
32768)
VAR
30 12 4 VAs, 3-Ph total SINT16 0 to +32767 (4500 /
32768)
VA
30 13 4 Power Factor,
3-Ph total
SINT16 -1000 to
+1000
0.001 None
30 14 4 Frequency SINT16 0 to 9999 0.01 Hz
Vista de pagina 251