Doc# E149701 B - 22
B: Modbus Map and Retrieving Logs
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Enable: 1 (Engage log)
Scope: 0 (Normal Mode)
---------------------------------------------------
Receive: 0106C34F0280 (echo)
NOTE: This engages the log for use on this COM Port, and latches the oldest record as
record index 0.
3. Read [0xC757, 16 reg], Availability is 0.
Send: 0103 C757 0010
Command:
Register Address: 0xC757
# Registers: 16
---------------------------------------------------
Receive: 010320 00000100 00000064 0012 0002
060717101511 060718101511
0000000000000000
Data:
Max Records: 0x100 = 256 records maximum.
Num Records: 0x64 = 100 records currently logged.
Record Size: 0x12 = 18 bytes per record.
Log Availability: 0x02 = 2, In use by COM2, RS485 (the current
port)
First Timestamp: 0x060717101511 = July 23, 2006, 16:21:17
Last Timestamp: 0x060717101511 = July 24, 2006, 16:21:17
NOTE: This indicates that the log has been engaged properly in step 2. Proceed to
retrieve the log.