Doc# E149701 C - 7
C: DNP Mapping
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Object 10 - Binary Output States
Read with Object 10, Var 2, and Qualifiers 0, 1, 2 or 6. (Included in Class 0
responses.)
Supported Flags:
Bit 0: ONLINE (0=Offline, 1=Online) (If the Input is not present it will be shown as
Offline.)
Bit 1: RESTART (1=The Object is in the Initial State and has not been updated since
Restart.)
Bit 7: STATE (0=Off, 1=On)
Object Point Var Description Format Range Multiplier Units Comments
10 0 2 Reset Energy
Counters
BYTE Always 1 N/A None
10 1 2 Change to
Modbus RTU
Protocol
BYTE Always 1 N/A None
10 2 2 Reset Demand
Cntrs (Max /
Min )
BYTE Always 1 N/A None
10 3 2 Read Relay 1
State RO1S
Relay 1
(expansion
port 1)
BYTE Bit Flags N/A None Returns the Status and
State of the Output in
the Flags.
10 4 2 Read Relay 2
State RO1S
Relay 2
(expansion
port 1)
BYTE Bit Flags N/A None Returns the Status and
State of the Output in
the Flags.
10 5 2 Read Relay 3
State RO1S
Relay 1
(expansion
port 2)
BYTE Bit Flags N/A None Returns the Status and
State of the Output in
the Flags.
10 6 2 Read Relay 4
State RO1S
Relay 2
(expansion
port 2)
BYTE Bit Flags N/A None Returns the Status and
State of the Output in
the Flags.