Doc# E149701 C - 8
C: DNP Mapping
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Object 12 - Control Relay Outputs
(Responds to Function 3 - Select, 4 - Operate, or 5 - Direct Operate; Count of 1 Only.)
(Control code 3 or 4, Qualifiers 17x or 28x, On - 0 msec; Off - 1 msec.)
(Only one control object at a time may be specified.)
Object Point Var Description Format Range Multiplier Units Comments
12 0 1 Reset Energy
Counters
N/A N/A N/A none Control Code 3 only
12 1 1 Change to
Modbus RTU
Protocol
N/A N/A N/A none Responds to Function 6
(Direct Operate - No
Ack), Qualifier Code
17x, Control Code 3,
Count 0, On 0 msec, Off
1 msec ONLY.
12 2 1 Reset Demand
Counters (Max
/ Min)
N/A N/A N/A none Control Code 3 only
12 3 1 Control Relay
1 RO1S Relay
1 (expansion
port 1)
N/A N/A N/A none See Section C.4 for
operation rules and
parameters.
12 4 1 Control Relay
2 RO1S Relay
2 (expansion
port 1)
N/A N/A N/A none See Section C.4 for
operation rules and
parameters.
12 5 1 Control Relay
3 RO1S Relay
1 (expansion
port 2)
N/A N/A N/A none See Section C.4 for
operation rules and
parameters.
12 6 1 Control Relay
4 RO1S Relay
2 (expansion
port 2)
N/A N/A N/A none See Section C.4 for
operation rules and
parameters.
Comentarios a estos manuales