B: Modbus Map and Retrieving Logs
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
In order to retrieve the meter's serial number, enter 40009 into the SCADA UI as the
starting register, and 8 as the number of registers.
• In order to work with SCADA and Driver packages that use the 40001 to 49999
method for requesting holding registers, take 40000 and add the value of the regis-
ter (Address) in the decimal column of the Modbus Map. Then enter the number
(e.g., 4009) into the UI as the starting register.
• For SCADA and Driver packages that use the 400001 to 465536 method for
requesting holding registers take 400000 and add the value of the register
(Address) in the decimal column of the Modbus Map. Then enter the number (e.g.,
400009) into the UI as the starting register. The drivers for these packages strip off
the leading four and subtract 1 from the remaining value. This final value is used as
the starting register or register to be included when building the actual modbus
message.
B.7: Modbus Register Map (MM-1 to MM-40)
The Shark® 200 meter's Modbus Register Map begins on the following page.