E: Using the IEC61850 Network Card
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
</Communication>
The node <P type="IP" xsi:type="tP_IP"> (bolded in the example above) defines the
meter’s IP address. This IP address must be the same as the IP address configured in
the meter’s Device Profile (see step 4 in Section E.4.1) for each IEC 61850 Protocol
Ethernet Network card in the meter.
Also, make sure that the iedName field in the ConnectedAp section (underlined in the
example) is the same as the name field defined in the IED section.
This is how the unit is assigned its name and IP address.
1. The Shark® 200 meter’s .icd file can be downloaded directly from the Shark® 200
unit. To do this, use a web browser and key:
http://aa.bb.cc.dd/
, where aa.bb.cc.dd is the IP address assigned to the IEC 61850 Protocol Ethernet
Network card (see Section E.4.1).
The Meter Information webpage is displayed.
NOTE: The firmware runtime version which is displayed in the Run Ver field of this
webpage determines the default password for Network card upgrading, uploading
the .cid file, and resetting the Network card.
Firmware
Runtime
Version