B: Modbus Map and Retrieving Logs
Doc# E149701 MM-1
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Description (Note 1) Format Range (Note 6) Units or Resolution Comments # Reg
read-only
0000 - 0007 1 - 8 Meter Name ASCII 16 char none 8
0008 - 000F 9 - 16 Meter Serial Number ASCII 16 char none 8
0010 - 0010 17 - 17 Meter Type UINT16 bit-mapped
------st -----vvv
t = transducer model (1=yes, 0=no),
s= submeter model(1=yes,0=no),
vvv = V-switch:
V1 = standard 200,
V2 = V1 plus logging,
V3 = V2 plus THD,
V4 = V3 plus relays,
V5 = V4 plus waveform capture up to 64 samples/cycle
and 3 Meg,
V6 = V4 plus waveform capture up to 512 samples/cycle
and 4 Meg
1
0011 - 0012 18 - 19 Firmware Version ASCII 4 char none 2
0013 - 0013 20 - 20 Map Version UINT16 0 to 65535 none 1
0014 - 0014 21 - 21 Meter Configuration UINT16 bit-mapped
-----ccc --ffffff
ccc = CT denominator (1 or 5),
ffffff = calibration frequency (50 or 60)
1
0015 - 0015 22 - 22 ASIC Version UINT16 0-65535 none 1
0016 - 0017 23 - 24 Boot Firmware Version ASCII 4 char none 2
0018 - 0018 25 - 25 Option Slot 1 Usage UINT16 bit-mapped same as register 10000
(0x270F)
1
0019 - 0019 26 - 26 Option Slot 2 Usage UINT16 bit-mapped same as register 11000
(0x2AF7)
1
001A - 001D 27 - 30 Meter Type Name ASCII 8 char none 4
001E - 0026 31 - 39 Reserved Reserved 9
0027 - 002E 40 - 47 Reserved Reserved 8
002F - 0115 48 - 278 Reserved Reserved 231
0116 - 0130 279 - 305
0131 - 01F3 306 - 500 Reserved Reserved 194
01F4 - 0203 501 - 516 Reserved Reserved 16
Fixed Data Section
Identification Block
Integer Readings Block occupies these registers, see below
Modbus Address
Hex Decimal