Doc# E149701 2 - 16
2: Meter Overview and Specifications
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
• ANSI C62.41 (Burst)
• EN61000-6-2 Immunity for Industrial Environments: 2005
• EN61000-6-4 Emission Standards for Industrial Environments: 2007
• EN61326 EMC Requirements: 2006
• KEMA Certified IEC 61850
2.4: Accuracy
(For full Range specifications see Section 2.2.)
Shark 200 Clock Accuracy: Max. +/-2 seconds per day at 25
o
C
For 23
o
C, 3 Phase balanced Wye or Delta load, at 50 or 60 Hz (as per order), 5A
(Class 10) nominal unit, accuracy as follows:
Table 2:
Parameter Accuracy Accuracy Input Range1
Voltage L-N [V] 0.1% of reading (69 to 480)V
Voltage L-L [V]
0.2% of reading
2
(120 to 600)V
Current Phase [A]
0.1% of reading
1, 3
(0.15 to 5) A
Current Neutral (calcu-
lated) [A]
2% of Full Scale
1
(0.15 to 5) A @ (45 to 65)
Hz
Active Power Total [W]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
Active Energy Total [Wh]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
Reactive Power Total
[VAR]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0 to 0.8)
lag/lead PF
Reactive Energy Total
[VARh]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0 to 0.8)
lag/lead PF
Apparent Power Total [VA]
0.2% of reading
1, 2
(0.15 to 5) A @ (69 to
480) V @ +/- (0.5 to 1)
lag/lead PF
Comentarios a estos manuales